2.4 electromagnetic compatibility
2.4.1 electrostatic discharge reactance
Through the GB/T 17626.21998 standard, electrostatic discharge immunity test IV.
2.4.2 radio frequency electromagnetic field radiated immunity
Through the GB/T 17626.31998 standard, RF electromagnetic field immunity test level 3.
2.4.3 electric fast transient pulse group immunity
GB/T 1998 - 17626.4 standard, electrical fast transient pulse group immunity test.
2.4.4 surge (impact) immunity
Through the GB/T 1999 - 17626.5 standard, surge (impact) immunity test 3.
Conduction disturbance degree of 2.4.5 RF field induction
Through the GB/T 17626.61998 standard, RF induction level 3 test conducted
2.4.6 power frequency magnetic field immunity
Through the GB/T 1998 - 17626.8 standard, the power frequency magnetic field immunity 5 level test
2.4.7 pulse magnetic field immunity
Through the GB/T 1998 - 17626.9 standard, the pulse magnetic field immunity 5 level test.
2.4.8 damped oscillatory magnetic field immunity
Through the GB/T 1998 - 17626.10 standard, damped oscillatory magnetic field immunity test 5 levels of test.
2.4.9 oscillation wave immunity
Through the GB/T 1998 - 4 standard, 17626.12 - level oscillation wave immunity test.
3.10 stator overvoltage protection
For generator, in particular to a hydro generator, after load rejection due to the speed control of speed control system can not keep up, is easy to appear the stator voltage exceeds the allowed range of over voltage phenomena; at this point to be equipped with over voltage protection, protection from the generator terminal voltage when any phase of more than setting value by setting the delay action to stop.
3.11 stator ground protection
Generator stator grounding protection can for the generator neutral point ungrounded or via arc suppression coil grounding grounding, protection from the generator end opening of the delta winding voltage when open delta windings voltage greater than setting value by setting the exit delay.
Three、Software function deion
3.1. differential quick break protection
When any phase difference current is greater than the value of the differential speed, the protection action is stopped. Fast removal of generators in the case of a serious fault in the area of the generator. Differential speed determine the value should be able to avoid the external fault of the maximum unbalanced current, and taking into account the current transformer saturation factor, generally take 3 to 8 times the rated current
3.2.Ratio differential protection
Using the conventional ratio differential principle, the equations of motion are as follows:
Id > Icd (Ir Ir0)
Id - Icd > Kcd ·(Ir- Ir0) (Ir ≥ Ir0)
At the same time to meet the above two equations, the ratio of the differential element action. Among them, Id for the differential current, Ir for the braking current, Kcd for
Ratio braking coefficient, Icd is the threshold value of the differential current, and Ir0 is the turning point of the current value.
device overview
SAI3880D series digital generator protection device with high performance chip supports universal hardware platform, easy to maintain; the Ethernet communication, high-speed data transmission and reliable. Complete localization of Chinese display technology, simple operation.
Based on waterproof, dust, anti vibration design, can be run in a variety of field conditions.
Suitable for capacity of 50MW and below the fire and hydro generator protection.
1.2 main features of the device
An Motorola 32 bit microcontroller technology, the stability and speed of products is guaranteed
The protection. The 14 bit a / D converter, optional measurement module dedicated to the A / D conversion accuracy is up to 24 bits and the measurement indicators easily reach
The purpose of configuration with high capacity RAM and Flash Memory, can record 8 to 50 recorded reports, record the number of events is not less than 1000
An independent tuning of 32 sets of protection setting value, safe and convenient switch
In high precision clock chip, and equipped with GPS hardware circuit for the whole time, system clock synchronization
It is equipped with high speed Ethernet communication interface, and the integration of IEC870-5-103 standard communication protocol
In the electrical design with the machine, no adjustable device
In high grade, quality assurance component selection
An excellent anti-interference performance, panel or installed in the switch cabinet without other anti-jamming module
The purpose of self diagnosis function perfect
The chassis design of waterproof and dustproof and anti vibration.
The purpose of debugging conceptual design
2.5 mechanical properties
2.5.1 vibration
The device can withstand the vibration endurance test of the I level of 16.3 in the GB7261.
2.5.2 impact
The device can withstand the impact endurance test of the I level of 17.5 in the GB7261.
2.5.3 collision
The device can withstand the impact endurance test of the GB7261 level of I in the eighteenth chapter.
2.6 environmental conditions
A) ambient temperature: Work: -40 C ~ 85.
Storage: 25 degrees to +70 degrees Celsius, in the limit value does not apply the amount of incentive, the device does not appear irreversible change
After the temperature is restored, the device should be able to work properly.
Relative humidity: the maximum monthly average relative humidity of 90%, while the average monthly average of.
The lowest temperature is 25 DEG C and no condensation surface. When the maximum temperature of +40 degrees Celsius, the average maximum relative humidity
Degree no more than 50%.
(c) atmospheric pressure: 86 to 106kPa (relative altitude below 2km)